The product is manufactured according to the standard of Gb 12706 or IEC, BS, DIN and ICEA upon request.
The product is suitable for use in power disrtibution networks or fixed installations for industrial equipments with rated voltage up to and including 35kV.
1. ● XLPE Insulated Electrical Cable for rated power frequency voltage Uo /U:3.6/6kV ~ 26/35kV.
● Max. Permissible continuous operating temperature of comductor: 90℃.
● Max. Short-circuit temperature of conductor shall not exceed 250℃.(5s Max. Duration)
● The ambient temperature under imstllation Shall not below 0℃
● The bending radius of single-core cable shall not less than 20 times of the cable diameter
The bending radius of three-cores cable shall not less than 15 times of the cable diameter
2. ● XLPE Insulated Electrical Cable for rated power frequency voltage Uo /U:0.6/lkV
● Max. Permissible comtinuous operating temperature of comductour:90℃
● Max. Short-circuit temperature of the conductor shall not exceed 250℃(5s maximum duration).
● The ambient temperature under installation shall not below 0℃
● The bending radius of a cable shall not less than 15 times of the cable diameter.
3. ● PVC Insulated Electical Cable for rated power frequency voltage Uo /U:03.6/1kV
● Max.permissible comtinuous operating temperature of conductor: 70℃
● Max.short-circuit temperature of the comductor shall not exceed: 160℃(5s maximum duration).
● The ambient temperature under installation shall not below 0℃
● The bending radius of a cable shall not be less than 10 times of the cable diameter.